How to calculate AHU CFM
To calculate AHU CFM (Cubic Feet per Minute), you determine the airflow required based on either the room volume and air changes per hour (ACH), or by using thermal load and temperature difference. Both methods are widely used in HVAC design and commissioning.
🧩 Methods of Calculating AHU CFM
🔹 Method 1 – Room Volume & ACH
This is the most common method for ventilation design.
Room Volume = Length × Width × Height (ft³)
ACH (Air Changes per Hour) = Number of times air is replaced per hour
Example: Room size = 20 ft × 15 ft × 10 ft = 3,000 ft³ ACH = 6 (typical for offices)
➡️ The AHU must supply 300 CFM to meet ventilation requirements.
🔹 Method 2 – Thermal Load (BTU/hr)
Used when sizing AHUs for cooling/heating loads.
BTU/hr = Heat load of the space
ΔT = Temperature difference between supply and return air
Example: Heat load = 24,000 BTU/hr ΔT = 20°F
➡️ The AHU must deliver 1111 CFM to handle the thermal load.
🔹 Method 3 – Differential Pressure & K‑Factor
Used in Testing, Adjusting, and Balancing (TAB) procedures with installed airflow measuring devices.
K = Device constant (provided by manufacturer)
ΔP = Differential pressure measured across the flow grid
Example: K = 1250, ΔP = 0.64 in. w.c.
➡️ The AHU supplies 1000 CFM, verified against design specs.
📊 Comparison of Methods
| Method | Formula | Best Use Case |
|---|---|---|
| Room Volume & ACH | (Room Volume × ACH) ÷ 60 | Ventilation design (offices, labs, hospitals) |
| Thermal Load (BTU/hr) | BTU/hr ÷ (1.08 × ΔT) | Cooling/heating load calculations |
| Differential Pressure & K‑Factor | K × √ΔP | Commissioning, TAB, field verification |
✅ Key Takeaway
Use Room Volume & ACH for ventilation design.
Use Thermal Load method for cooling/heating sizing.
Use Differential Pressure & K‑Factor for commissioning and field balancing.
Comments
Post a Comment