Dry Pipe Sprinkler System – Working Principle A Dry Pipe Sprinkler System is an automatic fire protection system designed primarily for areas where low or freezing temperatures could cause water-filled sprinkler pipes to freeze and become damaged. It is commonly used in locations such as cold storage areas, unheated spaces, parking areas, warehouses, and other temperature-sensitive environments. How the System Works Under normal conditions, the sprinkler piping is not filled with water . Instead, the pipes are maintained with pressurized air or nitrogen . Water is held on the supply side of a dry pipe valve , which prevents water from entering the sprinkler piping until the system is activated. When a fire occurs, the heat generated by the fire causes the nearest sprinkler head to reach its operating temperature. The sprinkler head then opens, releasing the pressurized air or nitrogen from the piping. As the compressed air pressure decreases, the pressure difference across t...
Gul Bahar Shah
Gul Bahar Shah
AHU Sensors: what they do, where to put them, and how to use them
1️⃣ Outside‑air T/RH 🌤️
• Purpose: economizer enable, coil reset, frost logic.
• Location: north side or shaded, away from exhausts and sun; use a shield.
• Spec: accuracy ±0.3–0.5 °C and ±2–3 %RH.
2️⃣ CO₂ sensor 🫁
• Purpose: demand‑controlled ventilation.
• Location: return duct or a representative zone.
• Setpoint: 800–1000 ppm typical; minimum OA per ASHRAE 62.1 still enforced.
3️⃣ Mixed‑air averaging sensor 🔀
• Purpose: detect low mixed‑air temperature, protect coils.
• Location: serpentine across the full plenum cross‑section upstream of the coil.
• Alarm: ~7–10 °C low limit; drive OA closed and enable preheat.
4️⃣ Freeze stat 🧊
• Purpose: coil freeze protection.
• Location: capillary laced on the leaving‑air face of the coil.
• Trip: 3–5 °C; action = stop supply fan, close OA, open heating/preheat valve.
5️⃣ Duct smoke detector 🚨
• Purpose: life safety interlock.
• Location: per NFPA 90A/72 and OEM spacing; avoid turbulent elbows; sample straight runs.
• Action: stop fans and close smoke/fire dampers.
6️⃣ Filter differential pressure 🧱
• Purpose: filter loading and alarms.
• Location: high side upstream, low side downstream; use proper pitot rings or static tips.
• Numbers: note clean DP (e.g., 90 Pa). Alarm at ≈2× clean DP or manufacturer limit.
7️⃣ Supply duct static pressure 📈
• Purpose: VAV static reset and fan control.
• Location: 2/3 of the main supply trunk; avoid takeoffs and elbows.
• Setpoint: 250–500 Pa typical VAV; reset to keep the “most‑open” VAV at ~90%.
• Fan law (plain text): ΔP ∝ Q^2, Power ∝ ΔP × Q.
8️⃣ Airflow/pressure switch (AFS) 💨
• Purpose: proof of airflow for safety sequences.
• Location: straight duct runs with correct pickup orientation.
• Setpoint: verify against design velocity; avoid nuisance trips at low flow.
9️⃣ Motor current switch ⚡
• Purpose: fan run status feedback to BMS.
• Setting: trip just below normal running current; avoids false “off” during soft‑start.
🔟 Duct temperature sensors 🌡️
• Purpose: supply, return, and discharge control and trending.
• Location: ≥5 duct diameters downstream of fittings; average or multi‑point in large ducts.
• Spec: ±0.3–0.5 °C; immersion wells for coils, strap‑on for casings.
1️⃣1️⃣ Space/Return RH sensor 💧
• Purpose: dehumidification, reheat, and IAQ alarms.
• Setpoints: comfort 40–60 %RH; critical spaces per ASHRAE 55 and project specs.
1️⃣2️⃣ Pressure transmitters (coils/fans) 🧪
• Use across coil to trend fouling; across fans to validate curves.
• Equation (plain text): Q = k × √(ΔP/ρ) for calibrated flow rings; document k.
Eg:
🏢 VAV AHU 40,000 m³/h, clean filter DP 90 Pa, design supply static 350 Pa.
• Static reset band: 250→350 Pa; trend fan kW before/after reset.
• Freeze stat trip: 4 °C; mixed‑air low limit: 8 °C.
• CO₂ DCV: setpoint 900 ppm; minimum OA = code value even at low occupancy.
• Filter alarm: 180 Pa; change‑out target 200 Pa.
• Purpose: economizer enable, coil reset, frost logic.
• Location: north side or shaded, away from exhausts and sun; use a shield.
• Spec: accuracy ±0.3–0.5 °C and ±2–3 %RH.
2️⃣ CO₂ sensor 🫁
• Purpose: demand‑controlled ventilation.
• Location: return duct or a representative zone.
• Setpoint: 800–1000 ppm typical; minimum OA per ASHRAE 62.1 still enforced.
3️⃣ Mixed‑air averaging sensor 🔀
• Purpose: detect low mixed‑air temperature, protect coils.
• Location: serpentine across the full plenum cross‑section upstream of the coil.
• Alarm: ~7–10 °C low limit; drive OA closed and enable preheat.
4️⃣ Freeze stat 🧊
• Purpose: coil freeze protection.
• Location: capillary laced on the leaving‑air face of the coil.
• Trip: 3–5 °C; action = stop supply fan, close OA, open heating/preheat valve.
5️⃣ Duct smoke detector 🚨
• Purpose: life safety interlock.
• Location: per NFPA 90A/72 and OEM spacing; avoid turbulent elbows; sample straight runs.
• Action: stop fans and close smoke/fire dampers.
6️⃣ Filter differential pressure 🧱
• Purpose: filter loading and alarms.
• Location: high side upstream, low side downstream; use proper pitot rings or static tips.
• Numbers: note clean DP (e.g., 90 Pa). Alarm at ≈2× clean DP or manufacturer limit.
7️⃣ Supply duct static pressure 📈
• Purpose: VAV static reset and fan control.
• Location: 2/3 of the main supply trunk; avoid takeoffs and elbows.
• Setpoint: 250–500 Pa typical VAV; reset to keep the “most‑open” VAV at ~90%.
• Fan law (plain text): ΔP ∝ Q^2, Power ∝ ΔP × Q.
8️⃣ Airflow/pressure switch (AFS) 💨
• Purpose: proof of airflow for safety sequences.
• Location: straight duct runs with correct pickup orientation.
• Setpoint: verify against design velocity; avoid nuisance trips at low flow.
9️⃣ Motor current switch ⚡
• Purpose: fan run status feedback to BMS.
• Setting: trip just below normal running current; avoids false “off” during soft‑start.
🔟 Duct temperature sensors 🌡️
• Purpose: supply, return, and discharge control and trending.
• Location: ≥5 duct diameters downstream of fittings; average or multi‑point in large ducts.
• Spec: ±0.3–0.5 °C; immersion wells for coils, strap‑on for casings.
1️⃣1️⃣ Space/Return RH sensor 💧
• Purpose: dehumidification, reheat, and IAQ alarms.
• Setpoints: comfort 40–60 %RH; critical spaces per ASHRAE 55 and project specs.
1️⃣2️⃣ Pressure transmitters (coils/fans) 🧪
• Use across coil to trend fouling; across fans to validate curves.
• Equation (plain text): Q = k × √(ΔP/ρ) for calibrated flow rings; document k.
Eg:
🏢 VAV AHU 40,000 m³/h, clean filter DP 90 Pa, design supply static 350 Pa.
• Static reset band: 250→350 Pa; trend fan kW before/after reset.
• Freeze stat trip: 4 °C; mixed‑air low limit: 8 °C.
• CO₂ DCV: setpoint 900 ppm; minimum OA = code value even at low occupancy.
• Filter alarm: 180 Pa; change‑out target 200 Pa.
- Get link
- X
- Other Apps
- Get link
- X
- Other Apps
Comments
Post a Comment