 Facility Management (FM) is a strategic discipline that combines maintenance, engineering, energy management, financial control, safety, service quality, and customer satisfaction. For a complex facility such as a hospital, the dashboard must also measure clinical-service continuity, critical utility reliability, and patient safety. The objective is to move from simply reporting completed work orders to measuring whether the facility is safe, reliable, efficient, and delivering value. 1. What is a Facility Management Master Dashboard? A Facility Management Master Dashboard is a centralized reporting system that consolidates operational data from the Computerized Maintenance Management System (CMMS), Building Management System (BMS), energy meters, finance records, safety inspections, and customer feedback. 12 It allows senior management, facility managers, maintenance managers, and engineering teams to answer questions such as: Are critical assets available when required? Are prev...

Fire Pump Types & Starting Pressure Sequence — Practical Fire Protection Engineering Guide

 Fire Pump Types & Starting Pressure Sequence — Practical Fire Protection Engineering Guide

Fire pumps are critical components of a building's fire protection system. They provide the required water flow and pressure to sprinkler systems, hydrants, standpipes and other approved firefighting systems when the available water supply cannot meet demand.

In hospitals, hotels, high-rise buildings and industrial facilities, correct pump selection, pressure settings, controller configuration and routine testing are essential for reliable fire protection.

Bombas de Incêndio: Critérios de Projeto e Desempenho | Nacional Fire
STCO | Structure Tone for Construction and Contracting
Products Details - Fire Trade
9

1. Main types of fire pumps

Home | Terra Crescent Fire and Safety

1. Electric main fire pump

The primary firefighting pump in an electrically driven arrangement. Its controller starts the pump automatically when system pressure falls to the configured start pressure.

Key points: Reliable power supply, approved controller, correct motor protection and starting arrangement, and compliance with the applicable fire-pump standard.

STCO | Structure Tone for Construction and Contracting

2. Diesel-engine-driven fire pump

Provides an alternative drive source where included in the approved design. It requires a suitable diesel engine, fuel supply, starting batteries, cooling, exhaust and ventilation.

Key point: It may be configured to start at a lower pressure than the electric pump, but the actual sequence must follow the approved design and applicable requirements.

Fire Fighting System Multistage Jockey and Electric Pump (PEJ 50Hz) Suppliers and Manufacturers - Factory Direct Price - Yeschamp Imp & Exp

3. Jockey pump

A small pressure-maintenance pump that compensates for minor leakage and small pressure fluctuations. It reduces unnecessary starts of the main fire pump.

Key point: It is not designed to supply the full firefighting demand and cannot replace the main fire pump.

Fire Protection & Firefighting Systems | Divyansh MEP

4. Water transfer pump

Transfers water between tanks or supply arrangements where required by the system design. A transfer pump does not automatically qualify as a listed fire pump or replace the required fire-pump installation.

2. Which pump starts first when pressure drops?

A typical arrangement uses pressure-based automatic starting. The exact sequence depends on the approved design, controller configuration and applicable code.

Normal condition

System pressure is maintained within its normal operating range.

Stage 1 — Jockey pump

Starts after a small pressure drop to restore system pressure.

Stage 2 — Main electric fire pump

Starts automatically when pressure falls to its configured start set point.

Stage 3 — Diesel fire pump, if provided

Starts at its configured set point if pressure continues to fall, including when the electric pump has failed or cannot meet demand.

Important engineering clarification: The diesel pump does not necessarily wait for an electrical failure signal. In a typical pressure-start arrangement, it responds to its own configured pressure set point. Therefore, it may start while the electric pump is running if system pressure falls sufficiently.

Fire pumps are generally expected to continue operating after automatic starting until they are stopped in accordance with the approved controller arrangement and applicable requirements. Do not assume they will automatically stop when pressure recovers.

3. Understanding fire pump pressure settings

There is no single starting pressure suitable for every building. Set points must be calculated from the system's hydraulic design and pump characteristics.

The following terms are important:

  • Jockey pump cut-in pressure: Pressure at which the jockey pump starts.

  • Jockey pump cut-out pressure: Pressure at which the jockey pump stops.

  • Main fire pump start pressure: Pressure at which the main fire pump controller initiates automatic starting.

  • Standby fire pump start pressure: Pressure at which the standby pump initiates starting, if the design uses pressure-based sequencing.

  • Churn pressure: Pump discharge pressure at zero flow, under the specified operating conditions.

  • Rated pressure: Pressure rise specified at the pump's rated flow and speed.

  • System design pressure: Pressure the system and its components are designed to accommodate, considering static head, pump pressure and other relevant conditions.

Illustrative pressure sequence

The following values are hypothetical and are not recommended set points for an actual installation.


Equipment

Example start pressure

Example stop behavior

Jockey pump

8.0 bar

Stops at its configured higher pressure

Main electric pump

7.0 bar

Normally requires an authorized stop procedure

Diesel standby pump

6.0 bar

Normally requires an authorized stop procedure


This example demonstrates the sequence only. Actual settings must account for water-supply pressure, pump churn pressure, elevation, hydraulic demand, component pressure ratings and applicable NFPA 20 requirements.

4. How to calculate the required pressure

For an initial engineering assessment, the static pressure required to overcome elevation can be estimated using:

\[ P=\rho g h \]

For water, a useful approximation is:

\[ \Delta P \approx 0.0981h \text{ bar} \]

where \(h\) is elevation in metres.

For example, a vertical rise of 30 m creates approximately:

\[ \Delta P=0.0981\times30=2.94\text{ bar} \]

This is only the static elevation component. The actual fire-pump design must also consider the required residual pressure at the hydraulically remote outlet, friction losses, fittings, backflow devices, system configuration and available water-supply pressure.

Do not size or set a fire pump using elevation alone. Hydraulic calculations and the approved pump curve are essential.

5. Main fire pump commissioning checklist

Commissioning checklist

0/12

Copy checklist

Testing must be performed by competent personnel using an approved procedure. Do not create a real fire-system pressure drop or start pumps without authorization, because testing can affect the building's fire protection and water supply.

6. Common operational problems

Problem

Possible causes

Recommended action

Jockey pump starts too frequently

Leakage, pressure fluctuation, incorrect settings or a faulty check valve

Inspect the system and review pressure trends

Main fire pump starts unexpectedly

Leakage, a genuine demand, pressure loss or incorrect settings

Investigate immediately and verify the cause

Electric pump fails to start

Power supply, controller, motor or starting-circuit fault

Follow the approved emergency procedure and inspect the controller

Diesel pump fails to start

Battery, starter, fuel, engine or controller problem

Check alarms and arrange competent troubleshooting

Both main and standby pumps run

High demand, pressure falling below both start points or a system fault

Verify actual demand and the approved sequence; do not disable a pump merely to stop it

Pressure remains low after pump starts

High demand, insufficient water supply, pump issue or major leakage

Assess the water supply, pump performance and system condition urgently


7. Applicable standards and final recommendation

The principal reference is NFPA 20 — Standard for the Installation of Stationary Pumps for Fire Protection, using the edition adopted by the authority having jurisdiction. Related standards may include NFPA 25 for inspection, testing and maintenance of water-based fire protection systems, plus local Civil Defence and building requirements.

For facility managers and MEP engineers, remember these five points:

  1. The jockey pump normally responds to small pressure losses first.

  2. The main fire pump starts at its approved pressure set point.

  3. A standby diesel pump may start at a lower set point if pressure continues to fall.

  4. Pressure settings must be coordinated with pump curves, hydraulic calculations and equipment pressure ratings.

  5. Verify the actual sequence during commissioning and document the results.

Never copy fire pump pressure settings from another building without checking the approved hydraulic design and controller requirements.

Comments

Popular posts from this blog

Detailed schematic diagram of a chilled water system,

  Detailed schematic diagram of a chilled water system, illustrating how chilled water is produced and circulated to a fan coil unit (FCU) for air conditioning. The system involves several components and stages: + System Flow Overview Chiller Plant: The chilled unit produces cold water, typically around 6-7°C (43-45°F), by removing heat through a refrigeration cycle. Pump Section: The primary CHW pump circulates the chilled water from the chiller into the distribution network. hashtag Activate to view larger image,

Identifying Electric Motor Wear and Failure

Identifying Electric Motor Wear and Failure Identifying Electric Motor Wear and Failure Introduction Signs of Wear and Failure Prevention Strategies Diagnostic Tools Contact Introduction Understanding how to identify wear and failure in electric motors is crucial for maintaining the efficiency and longevity of your equipment... Signs of Wear and Failure Unusual noises or vibrations. Excessive heat generation. Frequent tripping of circuit breakers. Decreased performance and efficiency. Visual signs of wear on components. Prevention Strategies Implementing regular maintenance schedules, usin...

The Importance of Electrical Maintenance in Industrial Settings

The Importance of Electrical Maintenance in Industrial Settings The Importance of Electrical Maintenance in Industrial Settings Overview Benefits Best Practices Conclusion Overview Electrical maintenance is crucial in industrial settings to ensure the safety, efficiency, and longevity of equipment. Regular maintenance helps prevent unexpected breakdowns and costly repairs. Benefits of Electrical Maintenance Improves safety by reducing the risk of electrical hazards. Enhances equipment efficiency and performance. Extends the lifespan of electrical components. Reduces downtime and operational costs. Best Practices for Electrical Maintenance ...