Skip to main content

Engineering: One System, Multiple Design Variables. An AHU is not just a box with a fan and cooling coil.

  Engineering: One System, Multiple Design Variables An AHU is not just a box with a fan and cooling coil. A small design mistake can increase: ✗ Fan power ✗ Pressure drop ✗ Noise ✗ Operating cost ✗ Maintenance frequency 1. Typical AHU Air Path Fresh Air → Louver → pre-Filter → Heat Recovery → Cooling/Heating Coil → Fan → Silencer → Supply Air Return/exhaust air paths must also be considered, especially where heat recovery, pressure control and IAQ are important. 2. Airflow Sizing The basic relationship is: Q = A × V Where: • Q = Airflow (m³/s) • A = Face area (m²) • V = Air velocity (m/s) Example: 20,000 m³/h = 5.56 m³/s At 2.5 m/s face velocity: Required area ≈ 2.22 m² Lower face velocity generally means a larger AHU footprint but can reduce component pressure drop and fan energy. ASHRAE notes that designers should not automatically default to 2.5 m/s; lower coil/filter velocities can provide energy benefits. (ASHRAE Handbook) 3. Pressure Drop = Hidden Energy Cost Typical AHU res...

There are several common types of electrical earthing (grounding) used in buildings, industries, hospitals, and power systems.

 There are several common types of electrical earthing (grounding) used in buildings, industries, hospitals, and power systems.


1. Plate Earthing

A copper or galvanized iron plate is buried in the ground and connected to the equipment using an earthing conductor.

  • Copper plate: commonly used where higher conductivity is required.
  • GI plate: economical and widely used.
  • Suitable for buildings and industrial installations.

2. Pipe Earthing

A GI or copper pipe is installed vertically into the ground and connected to the equipment.

  • One of the most common methods.
  • Economical and relatively easy to install.
  • Suitable for many building and industrial applications.

3. Rod Earthing

A copper, GI, or galvanized steel rod is driven into the ground.

  • Requires relatively little excavation.
  • Suitable where soil conditions permit deep electrode installation.
  • Multiple rods can be interconnected to reduce earth resistance.

4. Strip/Wire Earthing

A metal strip or wire is buried horizontally in a trench and used as the earth electrode.

  • Common for large installations.
  • Useful where a long horizontal earth electrode is practical.
  • Often used around substations and industrial facilities.

5. Chemical Earthing

An earthing electrode is installed with conductive backfill material around it to improve soil conductivity and maintain lower earth resistance.

  • Useful in high-resistivity soil.
  • Requires appropriate electrode and backfill selection.
  • Maintenance and environmental considerations should be addressed.

6. Grid/Mat Earthing

A network of interconnected conductors is buried below the ground.

  • Common in substations, power plants, and large industrial facilities.
  • Controls touch and step potentials.
  • Provides multiple paths for fault current.

7. Foundation Earthing

Earthing conductors or dedicated foundation electrodes are incorporated into the building foundation.

  • Provides an extensive earth-electrode system.
  • Particularly useful in new construction.
  • Must be coordinated with structural and electrical design.

Quick Comparison

TypeTypical Application
Plate EarthingBuildings/industrial installations
Pipe EarthingGeneral building installations
Rod EarthingBuildings, equipment, outdoor systems
Strip/Wire EarthingIndustrial installations/substations
Chemical EarthingHigh-resistivity soil
Grid/Mat EarthingSubstations/power plants
Foundation EarthingNew buildings

Important: Earthing requirements, electrode dimensions, conductor sizes, and acceptable earth resistance should be designed and tested according to the applicable local electrical code and standards such as IEC 60364, IEEE 80, and NFPA 70 (NEC), as applicable.


Comments

Popular posts from this blog

Detailed schematic diagram of a chilled water system,

  Detailed schematic diagram of a chilled water system, illustrating how chilled water is produced and circulated to a fan coil unit (FCU) for air conditioning. The system involves several components and stages: + System Flow Overview Chiller Plant: The chilled unit produces cold water, typically around 6-7°C (43-45°F), by removing heat through a refrigeration cycle. Pump Section: The primary CHW pump circulates the chilled water from the chiller into the distribution network. hashtag Activate to view larger image,

The Importance of Electrical Maintenance in Industrial Settings

The Importance of Electrical Maintenance in Industrial Settings The Importance of Electrical Maintenance in Industrial Settings Overview Benefits Best Practices Conclusion Overview Electrical maintenance is crucial in industrial settings to ensure the safety, efficiency, and longevity of equipment. Regular maintenance helps prevent unexpected breakdowns and costly repairs. Benefits of Electrical Maintenance Improves safety by reducing the risk of electrical hazards. Enhances equipment efficiency and performance. Extends the lifespan of electrical components. Reduces downtime and operational costs. Best Practices for Electrical Maintenance ...

Identifying Electric Motor Wear and Failure

Identifying Electric Motor Wear and Failure Identifying Electric Motor Wear and Failure Introduction Signs of Wear and Failure Prevention Strategies Diagnostic Tools Contact Introduction Understanding how to identify wear and failure in electric motors is crucial for maintaining the efficiency and longevity of your equipment... Signs of Wear and Failure Unusual noises or vibrations. Excessive heat generation. Frequent tripping of circuit breakers. Decreased performance and efficiency. Visual signs of wear on components. Prevention Strategies Implementing regular maintenance schedules, usin...